G90 vs G60 Type B Metal Deck: Which Should You Use in Florida?

Choose G60 for conditioned, enclosed buildings away from salt air. Choose G90 for coastal sites, open or unconditioned spaces, and roofs with wet-placed insulating fill. G90 carries a heavier zinc coating, so it protects longer. Structural capacity is the same for both at the same gauge. We supply 1.5" Type B in G60 and G90, 22 to 16 gauge.

Side by side

  • Coating: G60 and G90 are both ASTM A653 designations. The number is total zinc weight in hundredths of an ounce per square foot, so G90 has more zinc.
  • Strength: identical. Loads come from gauge and 50 ksi steel, not from the coating.
  • Typical G60 uses: inland offices, schools, retail and other conditioned interiors.
  • Typical G90 uses: coastal buildings, canopies, warehouses, parking structures, vented deck under lightweight concrete.
  • Cost drivers: G90 uses more zinc, so it is priced differently from G60. Get both priced if you are still deciding.

A Florida rule of thumb

If the deck underside breathes outdoor air, or the building is close enough to the water to see salt spray on cars, lean toward G90. The final call belongs to the engineer or architect of record, and the specification governs.

Send us your plans and we can price the takeoff in both coatings so the team can decide with real numbers.

Related Questions

Can G60 and G90 deck be mixed on one project?

Yes, if the documents allow it. For example, a design might use G90 at open canopies and G60 over the conditioned interior. Mark the areas clearly on the deck plan and shop drawings so bundles are not swapped in the field, and keep the coating on the deck labels.

Does vented Type B deck need G90?

Vented deck is used under lightweight insulating concrete, which brings water onto the deck. Galvanized deck is the norm for this, and many specifications call for G90. Check the insulating fill manufacturer's requirements and the project specification for the minimum coating.