What Shows 1.5-Inch B Deck Works Under Florida Coastal Wind?
The structural evidence for 1.5" Type B under coastal Florida wind is a set of documents: the catalog's ASD upward load tables calculated to SDI and AISI standards, published capacities for the specified fasteners, the roof assembly's wind uplift approval, and the engineer of record's calculations tying them to the design pressures. Ask us for the catalog data your package needs.
What goes in the evidence package
- Deck data sheet: section properties and upward load tables for the gauge used.
- Fastener data: uplift and shear values for the welds or screws on the drawings.
- Roof assembly approval showing the deck it was tested on.
- Engineer's calculations for field, edge and corner zones.
- Shop drawings showing sheet layout and fastening by zone.
Coastal considerations
Coastal sites have higher wind exposure and salt in the air. The catalog upward loads at 5'-0" spans in the table below show how much capacity rises with gauge. For corrosion, G90 galvanizing carries more zinc than G60 and is the usual pick near the coast; protect the deck from moisture until the roof is on.
Get the documents and the deck
We provide the catalog pages for the gauge you buy. Ask us for the documentation your permit requires, and send your plans for a quote.
1.5" Type B ASD uniform upward load at 5'-0" span, psf (catalog)
| Gauge | Single | Double | Triple |
|---|---|---|---|
| 22 | 138 | 132 | 165 |
| 20 | 177 | 176 | 220 |
| 18 | 249 | 239 | 299 |
| 16 | 315 | 308 | 385 |
Related Questions
Are the upward load values service or factored?
They are ASD allowable loads with a safety factor of 1.67, so they are compared with ASD-level wind pressures, not strength-level ones. The engineer of record converts the code wind pressures to the right level before comparing. The tables also do not include fastener capacity, which is checked separately.
Does the deck need a product approval in coastal Florida?
Requirements vary by jurisdiction and by whether the deck is part of an approved roof assembly. In the High-Velocity Hurricane Zone, roof assemblies need approval for that zone, and the deck must match what the approval lists. Ask us for the documentation your permit requires and confirm with your building department.