How Far Can Type B Metal Deck Span Under Florida Wind Loads?
Type B construction-load spans in our catalog run from 8'-03" at 22 gauge to 19'-03" at 16 gauge on a single span, and from 10'-02" to 23'-08" over double or triple spans. Spans for Florida wind uplift and roof live loads are a separate check made by the engineer of record with the full load tables. We supply the gauge your design requires.
Construction spans vs design spans
Construction spans are based on a 200 lb load on a 1 ft width of deck during erection, per ANSI/SDI RD-2017 and SD-2022. They limit how far deck can span before concrete, insulation or roofing is added. The service condition is a separate check: downward loads (dead, roof live, rain) and upward wind uplift, using the ASD load and deflection tables.
How wind uplift changes the answer
- Uplift is highest at roof corners and edges, so those zones may need shorter spans, heavier gauge or tighter fastening.
- Our catalog tabulates upward ASD loads for spans of 5'-0" to 10'-0"; for example, 20 ga in a triple span is listed at 153 psf upward at 6'-0".
- Fastener capacity and the deck's diaphragm role are checked separately from bending.
Get the gauges right
Send your structural drawings and we will quote the gauges and lengths the engineer specified.
Type B construction spans, 200 lb load on 1 ft width (ANSI/SDI RD-2017, SD-2022)
| Gauge | Single span | Double or triple span | Cantilever |
|---|---|---|---|
| 22 | 8'-03" | 10'-02" | 2'-02" |
| 20 | 11'-00" | 13'-07" | 2'-09" |
| 18 | 14'-11" | 18'-05" | 3'-10" |
| 16 | 19'-03" | 23'-08" | 4'-10" |
Related Questions
Why are double spans longer than single spans?
Deck continuous over an interior support shares moment between spans, so it is stiffer and stronger than a single simple span. That is why catalog construction spans are longer for double or triple conditions. Sheet lengths should be planned to get those continuous spans where possible.
What does the cantilever span mean?
It is the maximum overhang past the last support under the construction load in our catalog: 2'-02" for 22 ga up to 4'-10" for 16 ga. It is calculated with a 200 lb load and a 10 psf uniform load per ANSI/SDI.